Before You Test - Commissioning a Condensate Pump
Before any testing can begin, it’s essential to ensure that the condensate pump is properly installed. This includes safely mounting the unit. It also involves connecting the inlet and discharge lines. Finally, wire the power supply as the manufacturer says.
Once the installation is complete and you've gone through your checklist, you're ready to move on to testing the pump's performance.
This guide provides some best practices on commissioning a condensate pump.
Check List:
Check the pump installed has the flow rate for the condensate being produced. Most condensate pumps are not rated for 100% duty, we recommend that a duty cycle of 50:50 at peak times (i.e. the pump only runs at peak time 50% of the time). Consult the manufacturers' duty recommendations, if they don’t provide the information then never go above 60% on time.
Check the pump can handle the discharge length. Most tank condensate pumps use centrifugal pumps; the performance of this type of pumps can be negatively affected by how the discharge hose is laid out. A 90° degree bend on a discharge line can affect the flow rate by as much as 25%, multiple 90° bends can have a dramatic effect on flow rate and pumping head.
Having a horizontal run before any vertical lift can also cause reduction in flowrate and vertical lift. The best installation for centrifugal pumps is to come vertically out of the pump to the maximum head and then put a 10° - 20° decline on the discharge line. This will allow you to use gravity to move the condensate along a longer horizontal path.
Ensure the power supply feeding the condensate pump is suitably rated and protected with an electrical safety device. We also recommend the pump is fed also from a permanent supply, best practise it to feed the pump from a separate supply than the air handler, this can prevent water spillage if the air handler is switched off and the residual condensate on the cooling coils can be removed.
Check if the pump has a built-in check valve or one needs to be installed in the discharge line. Check valves prevent the condensate from feeding back into the tank once the pump has turned off. Most manufacturers include a check valve with the pump, but some don’t.
Ensure all liquid connections are secured and suitably clamped to prevent water leakages and working loose because of vibration.